Compliance Specifications

Product Safety Tests

Table 1. Product Safety Tests
Description Specification Level
IP Rating

IEC 61850-3 clause 6.6.2

IEC 60529 clause 6.11

ISO 20653:2013

IP20
Clearance and Creepage

IEC 61850-3 clause 6.6.1

IEC 62368-1, clause 6.4.2 & 5.4.3

Overvoltage Category II

Pollution Degree II

Impulse Voltage

IEC 61850-3 clause 6.6.3

IEEE 1613 clause 5.3

5 kV on auxiliary power supply and digital inputs

1 kV on station bus ports

Dielectric Voltage

IEC 61850-3 clause 6.6.4

IEEE 1613 clause 5.2

2 kV on auxiliary power supply and digital inputs

0.5 kV on station bus ports

Insulation Resistance IEC 60255-27 clause 10.6.4.4 ≥550MΩ at 500VDC
Protective Bonding IEC 61850-3 clause 6.6.5 Less than 0.1 Ω
Flammability IEC 61850-3 clause 6.6.6 V-1
Single Fault Condition IEC 61850-3 clause 6.6.7 12 VDC
Product Safety Standards IEC 62368-1 Product Safety Standard for Europe and North America

Electromagnetic Compatibility (EMC) Tests

Table 2. Electromagnetic Compatibility (EMC) Tests
Description Specification Level
European Compliance

EN 55032:2012

EN 55024:2010

CISPR 32:2012

CISPR 24:2010

Multimedia Class A Equipment
North America Compliance

FCC Part 15 Subpart B:2017

ICES-003:2017

Multimedia Class A Equipment
Radiated Emission

IEC 61850-3 clause 6.7.4

CISPR22 table 5/7

class A
Conducted Emission

IEC 61850-3 clause 6.7.4

CISPR22 table 1/3

class A
1 MHz Damped Oscillatory Wave

IEC 61850-3 clause 6.7.3

IEC 61000-4-18

IEEE 1613 clause 6

IEEE 1613.1 clause 5

2.5 kV CM, 1.0 kV DM HV/Telec.

2.5 kV CM, 2.5 kV DM Zone A

Electrostatic Discharges

IEC 61850-3 clause 6.7.3

IEC 61000-4-2

IEEE 1613 clause 8

IEEE 1613.1 clause 8

8 kV contact, 15 kV air
Radiated Radio Frequency Magnetic Field

IEC 61850-3 clause 6.7.3

IEC 61000-4-3

IEEE 1613 clause 7

IEEE 1613.1 clause 7

20 V/m
Fast Transient/Burst

IEC 61850-3 clause 6.7.3

IEC 61000-4-4

IEEE 1613 clause 6

IEEE 1613.1 clause 5

4 kV
Surge

IEC 61850-3 clause 6.7.3

IEC 61000-4-5

IEC 1613.1 clause 6

AC Power Ports:

  • 4 kV LE
  • 2 kV LL
DC Power Ports:
  • 4 kV LE
  • 2 kV LL
  • 2 kV LE (PoE 56VDC)
  • 1 kV LL (PoE 56VDC)
Signal Ports:
  • 4 KV LE
  • 1 KV LE (PoE)
Conducted Disturbance Induced by RF Fields

IEC 61850-3 clause 6.7.3

IEC 61000-4-6

IEEE 1613.1 clause 9

0.15-80 MHz at 10 V

27, 68 MHz at 10 V

Main Frequency Voltage, Common-mode Disturbances

IEC 61850-3 clause 6.7.3

IEC 61000-4-16

IEEE 1613.1 clause 12

30 V; 60 s

300 V; 1 s

Power Frequency Magnetic Field

IEC 61850-3 clause 6.7.3

IEC 61000-4-8

IEEE 1613.1 clause 10

100 A/m cont.;

1000 A/m 1s

D.C. Voltage Dips

IEC 61850-3 clause 6.7.3

IEC 61000-4-29

60%; 0.1 s

30%; 0.1 s

A.C. Voltage Dips

IEC 61850-3 clause 6.7.3

IEC 61000-4-11

60%; 50 c

30%; 1c

D.C. Voltage Interruptions

IEC 61850-3 clause 6.7.3

IEC 61000-4-29

100%; 0.05 s
A.C. Voltage Interruptions

IEC 61850-3 clause 6.7.3

IEC 61000-4-11

100%; 5/50 c
D.C. Ripple

IEC 61850-3 clause 6.7.3

IEC 61000-4-17

IEEE 1613 clause 4.2

10% Ur_dc

5% content (different calculation method)

Damped Oscillatory Magnetic Field

IEEE 1613.1 clause 11

IEC 61000-4-10

100 A/m (peak)
Burden for DC Power Supply

IEC 61850-3, clause 6.8.2

60W
Inrush Current

IEC 61850-3, clause 6.8.1.2/6.8.2.2

100 VAC peak 15.4 A ≤ 5 ms

240 VAC peak 32.4 A ≤ 5 ms

100 VDC peak 19.4 A ≤ 1 ms

240 VDC peak 52.8 A ≤ 1 ms

24 VDC peak 131 A ≤ 1 ms

48 VDC peak 262 A ≤ 1 ms

Climatic Environmental Tests

Table 3. Climatic Environmental Tests
Description Specification Level
Dry Heat Operational

IEC 61850-3 clause 6.9.3.1

IEC 60068-2-2, test Be

+85°C; 16 hours

Dry Heat Operational

IEEE 1613 clause 3.1.1

+85°C

Cold Operational

IEC 61850-3 clause 6.9.3.2

IEC 60068-2-1, test Ad

-40°C; 16 hours

Cold Operational

IEEE 1613 clause 3.1.1

-40°C

Dry Heat Storage

IEC 61850-3 clause 6.9.3.3

IEC 60068-2-2, test Bb

+85°C; 16 hours
Dry Heat Storage

IEEE 1613 clause 3.1.2

+85°C
Cold Storage

IEC 61850-3 clause 6.9.3.4

IEC 60068-2-1, test Ab

-40°C; 16 hours
Cold Storage

-40°C
Damp Heat, Steady State

IEC 61850-3 clause 6.9.3.6

IEC 60068-2-78 test Cab

+40°C; RH 93%, 10 days
Damp Heat, Cyclic

IEC 61850-3 clause 6.9.3.7

IEC 60068-2-78 test Db

IEEE 1613 clause 3.1.3

+55°C RH 93%;

+25°C RH 97%;

6 cycles, 96 hours

Mechanical Environmental Tests

Table 4. Mechanical Environmental Tests
Description Specification Level
Vibration Response

IEC 61850-3 clause 6.10.1

IEC 60255-21-1

0.5 g, 1 sweep cycle/axis, 3 axis, freq range 10-150Hz

Vibration Endurance

IEC 61850-3 clause 6.10.1

IEC 60255-21-1

1 g, 20 sweep cycle/axis, 3 axis, freq range 10-150Hz
Shock Response

IEC 61850-3 clause 6.10.2

IEC 60255-21-2

5 g, 11 ms duration/pulse, 6 pulses/axis, 3 axis
Shock Withstand

IEC 61850-3 clause 6.10.2

IEC 60255-21-2

15 g, 11 ms duration/pulse, 6 pulses/axis, 3 axis
Bump

IEC 61850-3 clause 6.10.2

IEC 60255-21-2

10 g, 16 ms duration/pulse, 2000 pulses/axis, 3 axis
Seismic, Single Axis Sweep

IEC 61850-3 clause 6.10.3

IEC 60255-21-3

Freq range: 1-35 Hz,

Cross-over freq: 8-9 Hz

Displacement: 3.5 mm[x], 1.5 mm [y]

Acceleration: 1.0 g [x], 0.5 g [y]

Number of sweep cycles per axis 1, number of axis 3

Vibration IEEE 1613 clause 9 V.S.3
Shock IEEE 1613 clause 9 100 mm

Altitude

Table 5. Altitude
Description Specification Level
Altitude

IEC 61850-3 section 4, table 1

IEC 61850-3 section 7.2, table 25

less than or equal to 2000 m

86 kPa to 106 kPa