The iMR350 has two terminal blocks. One serves to connect the HV power supplies, the other supports the LV, and MV options. This section documents how to safely connect a power source to the iMR350.
![]() |
Electrocution hazard—risk of death, serious personal injury and/or damage to the device. |
![]() |
Electrical hazard—risk of damage to equipment. Do not connect AC power cables to a 24 or 48 power supply terminal block. Damage to the power supply may occur. Caution access to wiring terminals and replaceable modules is restricted to skilled persons only. |
![]() |
Multiple power source—redundant power. Disconnect all power sources. |
![]() |
Different power sources shall be used to achieve the redundancy of power supplies. |
The relay contact of the terminal block connector is used to detect user-configured events. The switch provides fail open and fail close contacts to form relay circuits based on requirements. If the device is not powered, or if an active alarm is present, the relay de-energizes, therefore initiating the NO and NC states. The contacts are energized upon power up of the unit and remain energized unless a critical error occurs. One common application for this output is to raise an alarm if a power failure or removal of control power occurs.
All equipment must be installed according to applicable local wiring codes and standards.
Always use cables that are rated for the operating ambient temperature of 85°C.
For 100-240 VAC rated equipment, protection for earth fault is provided by max. 20 A branch circuit from AC input in building installation. The protection in the building installation is relied upon for short-circuit backup protection.
![]() |
L—stands for Live; N—stands for Neutral NO—Normally Open (open=open circuit=not creating a path for the current) NC—Normally Closed (open=short circuit=creating a path for the current) PE—Protective Earth (earth Ground point in the electrical circuit |
To establish AC power connection with the power source turned off, follow the steps below. When following the instructions, refer to Figure 1.
If an AC power supply has been installed in PS1, perform steps 2 through 4 on the left hand terminal block. Please note that if there are no DC power supplies installed on the iMR350 then the right hand terminal block will not be populated.
If an AC power supply has been installed in PS2, perform steps 5 through 7.
To keep the wires from pulling loose, use a small flat-blade screwdriver to tighten the wire-clamp screws on the front of the terminal block connector.
All equipment must be installed according to applicable local wiring codes and standards.
Always use cables that are rated for the operating ambient temperature of 85°C.
For 100-240 VAC rated equipment, protection for earth fault is provided by max. 20 A branch circuit from AC input in building installation. The protection in the building installation is relied upon for short-circuit backup protection.
![]() |
L—stands for Live; N—stands for Neutral NO—Normally Open (open=open circuit=not creating a path for the current) NC—Normally Closed (open=short circuit=creating a path for the current) PE—Protective Earth (earth Ground point in the electrical circuit |
To establish AC power connection with the power source turned off, follow the steps below. When following the instructions, refer to Figure 1.
If an AC power supply has been installed in PS1, perform steps 2 through 4 on the left hand terminal block. Please note that if there are no DC power supplies installed on the iMR350 then the right hand terminal block will not be populated.
If an AC power supply has been installed in PS2, perform steps 5 through 7.
To keep the wires from pulling loose, use a small flat-blade screwdriver to tighten the wire-clamp screws on the front of the terminal block connector.
Equipment must be installed according to applicable local wiring codes and standards.
With the power source turned off, refer to figure Figure 3 and perform the following steps:
For a DC Power Supply in PS1, carry out steps 1 through 2, by wiring the right hand terminal block. Please note that if there are no AC power supplies installed on the iMR350 then the left hand terminal block will not be populated.
If a DC Power Supply has been installed in PS2, perform the following steps.
After wiring is completed, perform the following:
Equipment must be installed according to applicable local wiring codes and standards.
With the power source turned off, refer to figure Figure 3 and perform the following steps:
For a DC Power Supply in PS1, carry out steps 1 through 2, by wiring the right hand terminal block. Please note that if there are no AC power supplies installed on the iMR350 then the left hand terminal block will not be populated.
If a DC Power Supply has been installed in PS2, perform the following steps.
After wiring is completed, perform the following:
![]() |
The earth ground connection must be verified by an electrical engineer or a service person skilled in electrical installation and grounding. If the device is used as cord-connected mains equipment, for reliable earthing, use it as:
|
The user shall be responsible for ensuring the integrity of any protective conductor connections before carrying out any other actions.