Description | Specification | Level |
---|---|---|
IP Rating | IEC 61850-3 clause 6.6.2 IEC 60529 clause 6.11 ISO 20653:2013 |
IP20 |
Clearance and Creepage | IEC 61850-3 clause 6.6.1 IEC 62368-1, clause 6.4.2 & 5.4.3 |
Overvoltage Category II Pollution Degree II |
Impulse Voltage | IEC 61850-3 clause 6.6.3 IEEE 1613 clause 5.3 |
5kV on auxiliary power supply and digital inputs 1kV on station bus ports |
Dielectric Voltage | IEC 61850-3 clause 6.6.4 IEEE 1613 clause 5.2 |
2kV on auxiliary power supply and digital inputs 0.5kV on station bus ports |
Insulation Resistance | IEC 60255-27 clause 10.6.4.4 | 500VDC |
Protective Bonding | IEC 61850-3 clause 6.6.5 | Less than 0.1 Ohms |
Flammability | IEC 61850-3 clause 6.6.6 | V1 |
Single Fault Condition | IEC 61850-3 clause 6.6.7 | 5VDC, 12VDC |
Product Safety Standards | IEC 62368-1 | Product Safety Standard for Europe and North America |
Description | Specification | Level |
---|---|---|
Radiated Emission | IEC 61850-3 clause 6.7.4 CISPR22 table 5/7 |
class A |
Conducted Emission | IEC 61850-3 clause 6.7.4 CISPR22 table 1/3 |
class A |
1 MHz Damped Oscillatory Wave | IEC 61850-3 clause 6.7.3 IEC 61000-4-18 IEEE 1613 clause 6 IEEE 1613.1 clause 5 |
2.5 kV CM, 1.0kV DM HV/Telec. 2.5 kV CM, 2.5kV DM Zone A |
Electrostatic Discharges | IEC 61850-3 clause 6.7.3 IEC 61000-4-2 IEEE 1613 clause 8 IEEE 1613.1 clause 8 |
8kV contact, 15kV air |
Radiated Radio Frequency Magnetic Field | IEC 61850-3 clause 6.7.3 IEC 61000-4-3 IEEE 1613 clause 7 IEEE 1613.1 clause 7 |
20 V/m |
Fast Transient/Burst | IEC 61850-3 clause 6.7.3 IEC 61000-4-4 IEEE 1613 clause 6 IEEE 1613.1 clause 5 |
4kV |
Surge | IEC 61850-3 clause 6.7.3 IEC 61000-4-5 IEC 1613.1 clause 6 |
Power Ports: 4kV LE, 2kV LL Signal Ports: 2KV LE, 1KV LL |
Conducted Disturbance Induced by RF Fields | IEC 61850-3 clause 6.7.3 IEC 61000-4-6 IEEE 1613.1 clause 9 |
0.15-80MHz at 10V 27, 68 MHz at 10V |
Main Frequency Voltage, Common-mode Disturbances | IEC 61850-3 clause 6.7.3 IEC 61000-4-16 IEEE 1613.1 clause 12 |
30V; cont. 300V; 1s |
Power Frequency Magnetic Field | IEC 61850-3 clause 6.7.3 IEC 61000-4-8 IEEE 1613.1 clause 10 |
100 A/m cont.; 1000 A/m 3s |
D.C. Voltage Dips | IEC 61850-3 clause 6.7.3 IEC 61000-4-29 |
60%; 0.1s 30%; 0.1s |
A.C. Voltage Dips | IEC 61850-3 clause 6.7.3 IEC 61000-4-11 |
60%; 50 c 30%; 1c |
D.C. Voltage Interruptions | IEC 61850-3 clause 6.7.3 IEC 61000-4-29 |
100%; 0.05s |
A.C. Voltage Interruptions | IEC 61850-3 clause 6.7.3 IEC 61000-4-11 |
100%; 5/50c |
D.C. Ripple | IEC 61850-3 clause 6.7.3 IEC 61000-4-17 IEEE 1613 clause 4.2 |
10% Ur_dc 5% content (different calculation method) |
Damped Oscillatory Magnetic Field | IEEE 1613.1 clause 11 IEC 61000-4-10 |
100 A/m (peak) |
Description | Specification | Level |
---|---|---|
Dry Heat Operational | IEC 61850-3 clause 6.9.3.1 IEC 60068-2-2, test Bd |
+85°C; 16 hours |
Dry Heat Operational | IEEE 1613 clause 3.1.1 | +85°C |
Cold Operational | IEC 61850-3 clause 6.9.3.2 IEC 60068-2-1, test Ad |
-40°C; 16 hours |
Cold Operational | IEEE 1613 clause 3.1.1 | -40°C |
Dry Heat Storage | IEC 61850-3 clause 6.9.3.3 IEC 60068-2-2, test Bb |
+85°C; 16 hours |
Dry Heat Storage | IEEE 1613 clause 3.1.2 | +85°C |
Cold Storage | IEC 61850-3 clause 6.9.3.4 IEC 60068-2-1, test Ab |
-40°C; 16 hours |
Cold Storage | IEEE 1613 clause 3.1.2 |
-40°C |
Change of Temperature | IEC 61850-3 clause 6.9.3.5 IEC 60068-2-14 test Nb |
-40°C; +85°C 3 hours; 5 cycles |
Damp Heat, Steady State | EC 61850-3 clause 6.9.3.6 IEC 60068-2-78 test Cab |
+40°C; 93%, 10 days |
Damp Heat, Cyclic | IEC 61850-3 clause 6.9.3.7 IEC 60068-2-78 test Db IEEE 1613 clause 3.1.3 |
+55°C RH 95%; 6 cycles, 96 hours |
Description | Specification | Level |
---|---|---|
Vibration Response | IEC 61850-3 clause 6.10.1 IEC 60255-21-1 |
class 1 0.5g, 10Hz - 150Hz, 1 Octave/min, 1 sweep cycle in each axis, 8min per perpendicular axis |
Vibration Endurance | IEC 61850-3 clause 6.10.1 IEC 60255-21-1 |
class 1 1g, 10 - 150Hz, 1 Octave/min, 20 sweep cycles in each axis, 160min per perpendicular axis |
Shock Response | IEC 61850-3 clause 6.10.2 IEC 60255-21-2 |
class 1 5g, 11ms, half-sine, 3 shocks/direction/axis (18 total) |
Shock Withstand | IEC 61850-3 clause 6.10.2 IEC 60255-21-2 |
class 1 15g, 11ms, half-sine, 3 shocks/direction/axis(18 total) |
Bump | IEC 61850-3 clause 6.10.2 IEC 60255-21-2 |
class 1 10g, 16ms, half-sine, 1000 pulses |
Seismic, Single Axis Sweep | IEC 61850-3 clause 6.10.3 IEC 60255-21-3 |
class 1 Freq range: Nominal Range 5-35Hz, Cross Over: 8-9HzPeak Displacement: Below cross-overfrequency: 3.5mm[x] x 1.5mm [y] Sweep: 1 Cycle/Axis (x,y,z), 1 Octave/min |
Vibration | IEEE 1613 clause 9 | V.S.3 |
Shock | IEEE 1613 clause 9 | 100 mm |
Description | Specification | Level |
---|---|---|
Altitude | IEC 61850-3 section 4, table 1 IEC 61850-3 section 7.2, table 25 |
less than or equal to 2000m 86 kPa to 106 kPa |